CONDUCTOR: Solid bare copper.
INSULATION: Low smoke PVC.
VOLTAGE: 300 V.
COLOR: Red.
JACKET: Low smoke PVC 75° C.
UL: FPLP.
CONSTRUCTION: Conductors cabled. Overall shield of 100% aluminum polyester foil with a stranded tinned copper drain wire.
USES: For use in air plenums without conduit for fire alarm systems in compliance with the National Fire Protective Association and the National Electric Code, NEC article 760 type FPLP
| Catalog No. | AWG Size | Insulation Thickness | Jacket Thickness | No. of Cond. | Nominal O.D. | Put Up | Weight | Color Code |
|---|---|---|---|---|---|---|---|---|
| 504-67FAP | 18 |
0.010 in 0.254 mm |
0.013 in 0.330 mm |
2 |
0.150 in 3.81 mm |
1000 ft |
22 lbs/1000 ft 33 kgs/km |
Chart 1 |
| 504-72FAP | 18 |
0.010 in 0.254 mm |
0.013 in 0.330 mm |
4 |
0.180 in 4.57 mm |
1000 ft |
36 lbs/1000 ft 54 kgs/km |
Chart 1 |
| 504-74FAP | 16 |
0.010 in 0.254 mm |
0.013 in 0.330 mm |
2 |
0.170 in 4.32 mm |
1000 ft |
31 lbs/1000 ft 46 kgs/km |
Chart 1 |