a1102

M9X006

2.0 mm subunit – Riser

MECHANICAL, ENVIRONMENTAL & FLAME CHARACTERISTICS:

Crush Resistance                   EIA-455-41                        2,000 Newtons/cm
Impact Resistance                  EIA-455-25                        2,000 Impacts with 1.6 newton-meter
Flexure                                       EIA-455-104                      2,000 Cycles minimum
Minimum Bend Radius          Long-term – No Load       10 x Cable diameter
Minimum Bend Radius          Short-term – Load             15 x Cable diameter
Operating Temperature                                                      -20° C to 70° C
Storage Temperature                                                          -40° C to 80° C
UL Rated                                   Type OFNR
Flame Resistance                   UL 1666                              Passed
USES: Riser wiring (typically under 300 meters), office wiring, and computer room wiring.

PRODUCT FEATURES: 900 µm tight buffered fibers. Color coded for easy termination. Flame-retardant. UL listed for code compliance. Direct connectorization. 2-12 fibers per DEC specifications.

For “X” in part number, see optical characteristics chart

Specifications

Minimum Bend Radius - Long Term
3.1 in
7.9 cm
Minimum Bend Radius - Short Term
4.7 in
12 cm
Fiber Count
4
For X in Part Number use…
Maximum Load (Installation)
600 lbs
2,669 N
Outside Diameter
0.312 in
7.92 mm
Weight
25 lbs/1000 ft
37 kgs/km

Request Information