1007 | 30 – 16 | 300 | 80°C | 1/64 | PVC | Internal wiring of appliances |
1009 | 28 – 16 | 300 | 90°C | 1/64 | PVC | Internal wiring of appliances |
1010 | 28 – 16 | 300 | 105°C | 1/64 | PVC / nylon | Internal wiring of appliances |
1011 | 28 – 9 | 600 | 80°C | 1/32 | PVC | Internal wiring of appliances |
1012 | 28 – 9 | 600 | 80°C | 1/32 | PVC / nylon | Internal wiring of appliances |
1013 | 28 – 9 | 600 | 90°C | 1/32 | PVC | Internal wiring of appliances |
1014 | 28 – 9 | 600 | 90°C | 1/32 | PVC / nylon | Internal wiring of appliances |
1015 | 28 – 9 | 600 | 105°C | 1/32 | PVC | Internal wiring of appliances |
1016 | 28 – 9 | 600 | 105°C | 1/32 | PVC / nylon | Internal wiring of appliances |
1024 | 22 – 8 | 600 | 80°C | 3/64 | PVC | Internal wiring of appliances |
1028 | 22 – 8 | 600 | 105°C | 3/64 | PVC | Internal wiring of appliances |
1061 | 30 – 16 | 300 | 80°C | 0.009″ | Semirigid PVC | Internal wiring of machines |
1095 | 30 – 16 | 300 | 80°C | 0.012″ | PVC | Internal wiring of machines |
1096 | 30 – 16 | 300 | 80°C | 0.012″ | PVC / nylon | Internal wiring of machines |
1164 | 28 – 12 | 300 | 150°C | 0.013″ | TFE | Office appliances |
1180 | 28 – 10 | 300 | 200°C | 0.013″ | TFE | Office appliances |
1198 | 26 – 8 | 600 | 150°C | 0.020″ | TFE | Office appliances |
1199 | 26 – 8 | 600 | 200°C | 0.020″ | TFE | Office appliances |
1212 | 32 – 20 | Not rated | 80°C | 0.008″ | TFE | Office appliances |
1213 | 32 – 20 | Not rated | 105°C | 0.008″ | TFE | Office appliances |
1226 | 32 – 20 | Not rated | 80°C | 0.010″ | FEP | Back panel wiring |
UL STYLE NUMBER |
AWG SIZE |
VOLTAGE RATING |
TEMP. RATING |
INSULATION |
REMARKS |
|
THICKNESS | MATERIAL | |||||
1227 | 30 – 20 | Not rated | 105°C | 0.010″ | FEP | Back panel wiring |
1293 | 30 – 20 | Not rated | 105°C | 0.010″ | FEP / nylon | Office equipment |
1294 | 26 – 20 | Not rated | 80°C | 0.010″ | FEP / nylon | Office equipment |
1327 | 30 – 16 | Not rated | 105°C | 0.010″ | Kynar® | Office appliances |
1330 | 28 – 10 | 600 | 150°C | 0.020″ | FEP | Office equipment |
1331 | 28 – 10 | 600 | 200°C | 0.020″ | FEP | Office equipment |
1332 | 28 – 10 | 300 | 200°C | 0.013″ | FEP | Office equipment |
1333 | 28 – 10 | 300 | 150°C | 0.013″ | FEP | Office equipment |
1351 | 30 – 16 | Not rated | 80°C | 0.010″ | Kynar® | Office appliances |
1354 | – | 30 | 60°C | – | – | Coaxial cable |
1355 | 32 – 20 | Not rated | 200°C | 0.0055″ | FEP – polyimide |
|
1371 | 32 – 6 | Not rated | 105°C | 0.0055 – 0.020″ | FEP | |
0.006 – 0.020″ | PTFE | |||||
1394 | 32 – 20 | Not rated | 200°C | 0.0055″ | PTFE – polyimide |
|
1422 | 32 – 20 | Not rated | 105°C | 0.005″ | Kynar® | Back panel wiring |
1423 | 32- 20 | Not rated | 105°C | 0.004″ | Kynar® | Back panel wiring |
1426 | 32 – 20 | Not rated | 105°C | 0.006″ | Kynar® | Back panel wiring |
1429 | 30 – 16 | 150 | 80°C | 0.010″ | Irradiated PVC | Internal wiring of appliances |
1430 | 30 – 16 | 300 | 105°C | 0.015″ | Irradiated PVC | Internal wiring of appliances |
1431 | 30 – 10 | 600 | 105°C | 0.030″ | Irradiated PVC | Motor lead |
1431 | 8 | 600 | 105°C | 0.045″ | Irradiated PVC | Motor lead |
1431 | 6 – 2 | 600 | 105°C | 0.060″ | Irradiated PVC | Motor lead |
1431 | 1 – 1/0 | 600 | 105°C | 0.078″ | Irradiated PVC | Motor lead |
Kynar® is a registered trademark of Pennwalt Corporation.
UL STYLE NUMBER |
AWG SIZE RANGE |
VOLTAGE RATING |
TEMP. RATING |
INSULATION | REMARKS | |
THICKNESS | MATERIAL | |||||
1508 | 30 – 20 | 30 | 105°C | 0.0055″ | ETFE | Back panels for computers |
1512 | 16 – 14 | Not rated | 105°C | 0.010″ | PTFE | |
1513 | 30 – 20 | Not rated | 105°C | 0.0045″ | ETFE | Back panels for computers |
1516 | 30 – 20 | Not rated | 105°C | 0.004″ | ETFE | Back panels for computers |
1517 | 30 – 20 | Not rated | 105°C | 0.006″ | ETFE | Back panels for computers |
1523 | 30 – 20 | Not rated | 105°C | 0.005″ | ETFE | Back panels for computers |
1534 | 30 – 14 | Not rated | 80°C | 0.010″ | Irradiated PVC |
Internal wiring of appliances |
1536 | 30 – 10 | Not rated | 80°C | 0.010″ | Irradiated PVC |
Internal wiring of appliances |
1538 | 32 – 6 | 125 | 105°C | 0.0055 – 0.020″ |
FEP or PFA | |
36 – 8 | 125 | 105°C | PTFE | |||
1570 | 24 – 8 | 600 | 250°C | 0.020 – 0.030″ |
PTFE (mineral filled) |
|
1577 | 32 – 16 | Not rated | 200°C | 0.012″ | FEP or PTFE | |
1558 | 32 – 20 | Not rated | 125°C | 0.004″ | ETFE | |
1584 | 32 – 10 | 1,000 | 200°C | 0.022″ | PTFE | |
1586 | 36 – 6 | Not rated | 105°C | 0.0055 – 0.020″ |
ETFE | |
1591 | 32 – 16 | 300 | 150°C | 0.016″ | FEP | |
1592 | 32 – 16 | 300 | 200°C | 0.016″ | FEP | |
1609 | 36 – 6 | 125 | 105°C | 0.0055 – 0.020″ |
ETFE | |
1610 | 32 – 10 | Not rated | 105°C | 0.010″ | ETFE | |
1643 | 32 – 4/0 | 300 | 150°C | 0.13 – 0.030″ |
ETFE | |
1644 | 30 – 4/0 | 600 | 150°C | 0.020 – 0.045″ |
ETFE | |
1659 | 26 – 8 | 600 | 250°C | 0.020 – 0.030″ |
PTFE | |
1671 | 32 – 10 | 300 | 150°C | 0.010″ | ETFE |
UL STYLE NUMBER |
AWG SIZE RANGE |
VOLTAGE RATING |
TEMP. RATING |
INSULATION | REMARKS | |
THICKNESS | MATERIAL | |||||
1709 | 32 – 10 | 300 | 200°C | 0.013″ | PFA | |
1710 | 30 – 4/0 | 600 | 200°C | 0.020 – 0.045″ |
PFA | |
1716 | 36 – 6 | 150 | 150°C | 0.0055 – 0.020″ |
FEP or PFA or PTFE |
|
1726 | 32 – 4/0 | 300 | 250°C | 0.013 – 0.045″ |
PFA | |
1727 | 32 – 4/0 | 600 | 250°C | 0.020 – 0.045″ |
PFA | |
1814 | 32 – 20 | 150 | 150°C | 0.006″ | ETFE | |
1815 | 32 – 10 | 300 | 250°C | 0.013″ | PTFE | |
1828 | 32 – 10 | 300 | 150°C | 0.013″ | ETFE | |
1829 | 32 – 10 | 600 | 150°C | 0.020″ | ETFE | |
1857 | 32 – 16 | 150 | 150°C | 0.010″ | PFA | |
1858 | 32 – 10 | 300 | 150°C | 0.013″ | PFA | |
1859 | 32 – 4/0 | 600 | 150°C | 0.020 – 0.045″ |
PFA | |
1860 | 32 – 16 | 150 | 200°C | 0.010″ | PFA | |
1875 | 32 – 20 | 30 | 105°C | 0.0055″ | PTFE (expanded) |
|
2095 | 30 – 16 | 300 | 80°C | 1/64 | PVC | 2 conductor shielded PVC jacket |
2096 | 30 – 16 | 300 | 80°C | 1/64 | PVC | 3 conductor shielded PVC jacket |
2097 | 30 – 16 | 300 | 80°C | 1/64 | PVC | 4 conductor shielded PVC jacket |
2098 | 26 – 16 | 300 | 90°C | 1/64 | PVC | 2 conductor shielded PVC jacket |
2099 | 26 – 16 | 300 | 90°C | 1/64 | PVC | 3 conductor shielded PVC jacket |
2100 | 26 – 16 | 300 | 90°C | 1/64 | PVC | 4 conductor shielded PVC jacket |
2101 | 26 – 16 | 300 | 105°C | 1/64 | PVC | 2 conductor shielded PVC jacket |
2102 | 26 – 16 | 300 | 105°C | 1/64 | PVC | 3 conductor shielded PVC jacket |
UL STYLE NUMBER |
AWG SIZE RANGE |
VOLTAGE RATING |
TEMP. RATING |
INSULATION | REMARKS | |
THICKNESS | MATERIAL | |||||
2103 | 26 – 16 | 300 | 105°C | 1/64 | PVC | 4 conductor shielded PVC jacket |
2106 | 26 – 16 | 600 | 60°C | 1/32 | PE | 2 conductor shielded PVC jacket |
2107 | 26 – 16 | 600 | 60°C | 1/32 | PE | 3 conductor shielded PVC jacket |
2108 | 26 – 16 | 600 | 60°C | 1/32 | PE | 4 conductor shielded PVC jacket |
2115 | 26 – 16 | 600 | 80°C | 1/32 | PVC | 2 conductor shielded PVC jacket |
2116 | 26 – 16 | 600 | 80°C | 1/32 | PVC | 3 conductor shielded PVC jacket |
2117 | 26 – 16 | 600 | 80°C | 1/32 | PVC | 4 conductor shielded PVC jacket |
2343 | 30 minimum | Not rated | 80°C | – | – | Computer cable 0.060″ PVC jacket |
2344 | 30 minimum | Not rated | 80°C | – | – | Computer cable 0.080″ PVC jacket |
2345 | 30 minimum | Not rated | 80°C | – | – | Computer cable 0.110″ PVC jacket |
2346 | 30 minimum | Not rated | 80°C | – | – | Computer cable 0.140″ PVC jacket |
2384 | 30 minimum | 300 | 60°C | – | – | Computer cable 0.035″ PVC jacket |
2385 | 30 minimum | 300 | 60°C | – | – | Computer cable 0.060″ PVC jacket |
2386 | 30 minimum | 300 | 60°C | – | – | Computer cable 0.080″ PVC jacket |
2387 | 30 minimum | 300 | 60°C | – | – | Computer cable 0.110″ PVC jacket |
2388 | 30 minimum | 300 | 60°C | – | – | Computer cable 0.140″ PVC jacket |
2448 | 30 minimum | 30 | 60°C | – | – | Low voltage computer cable |
2461 | 26 – 16 | 300 | 80°C | – | – | 2 – 61 conductor PVC jacket |
2462 | 24 – 16 | 300 | 60°C | – | – | 2 – 61 conductor PVC jacket |
2463 | 26 – 16 | 600 | 80°C | – | – | 2 – 19 conductor PVC jacket |
2464 | 30 – 16 | 300 | 80°C | – | – | Multi-conductor control cable PVC |
2490 | 30 – 16 | Not rated | 60°C | – | – | Multi-conductor control cable PVC |
2493 | 30 – 16 | Not rated | 60°C | – | – | Multi-conductor control cable PVC |
UL STYLE NUMBER |
AWG SIZE RANGE |
VOLTAGE RATING |
TEMP. RATING |
INSULATION | REMARKS | |
THICKNESS | MATERIAL | |||||
2501 | 30 minimum | 600 | 105°C | – | – | Multi-conductor control cable PVC |
2502 | 40 minimum | 30 | 80°C | – | – | Multi-conductor control cable PVC |
2507 | 32 – 26 | Not rated | 105°C | – | – | Multi-conductor control cable PVC |
3068 | 26 – 20 | 300 | 105°C | 0.016″ | Silicone rubber / glass braid |
Internal wiring of appliances |
3069 | 26 – 20 | 600 | 150°C | 0.032″ | Silicone rubber / glass braid |
Internal wiring of appliances |
3070 | 18 – 12 | 600 | 150°C | 0.032″ | Silicone rubber / glass braid |
Internal wiring of appliances |
3071 | 18 – 14 | 600 | 200°C | 0.032″ | Silicone rubber / glass braid |
Internal wiring of appliances |
3074 | 12 | 600 | 200°C | 0.032″ | Silicone rubber / glass braid |
Internal wiring of appliances |
3075 | 10 | 600 | 200°C | 0.032″ | Silicone rubber / glass braid |
Internal wiring of appliances |
3101 | 10 | 600 | 150°C | 0.048″ | Silicone rubber / glass braid |
Internal wiring of appliances |
3122 | 26 – 20 | 300 | 200°C | 0.016″ | Silicone rubber / glass braid |
Internal wiring of appliances |
3123 | 30 – 16 | 600 | 150°C | 0.030″ | Silicone rubber | Internal wiring of appliances |
3132 | 30 – 16 | 300 | 150°C | 0.015″ | Silicone rubber | Internal wiring of appliances |
3133 | 30 – 16 | 600 | 150°C | 0.030″ | Silicone rubber | Internal wiring of appliances |
3134 | 18 – 12 | 600 | 150°C | 0.032″ | Silicone rubber | Internal wiring of appliances |
3135 | 18 – 12 | 600 | 200°C | 0.032″ | Silicone rubber | Internal wiring of appliances |
3136 | 26 – 20 | 300 | 150°C | 0.048″ | Silicone rubber | Internal wiring of appliances |
3137 | 26 – 20 | 600 | 150°C | 0.048″ | Silicone rubber | Internal wiring of appliances |
3138 | 18 – 12 | 600 | 150°C | 0.048″ | Silicone rubber | Internal wiring of appliances |
3139 | 18 – 12 | 600 | 200°C | 0.048″ | Silicone rubber | Internal wiring of appliances |
3142 | 18 – 12 | 600 | 150°C | 0.064″ | Silicone rubber | Internal wiring of appliances |
3143 | 18 – 12 | 600 | 200°C | 0.064″ | Silicone rubber | Internal wiring of appliances |
3167 | 26 – 9 | 600 | 105°C | 0.032″ | XLPE | Internal wiring of appliances |
UL STYLE NUMBER |
AWG SIZE RANGE |
VOLTAGE RATING |
TEMP. RATING |
INSULATION |
REMARKS | |
THICKNESS | MATERIAL | |||||
3168 | 18 – 12 | 1000 | 90°C | 0.032″ | XLPE | Internal wiring of appliances |
3173 | 26 – 9 | 600 | 125°C | 0.032″ | XLPE | Internal wiring of appliances |
3182 | 26 – 9 | 600 | 125°C | 0.048″ | XLPE | Internal wiring of appliances |
3195 | 8 | 600 | 125°C | 0.048″ | XLPE | Internal wiring of appliances |
3196 | 7 – 4 | 600 | 125°C | 0.064″ | XLPE | Internal wiring of appliances |
3239 | 24 – 10 | 10,000 – 20,000 |
200°C | 0.018 – 0.024″ |
FEP (modified) |
|
5107 | 22 – 4/0 | 600 | 200°C / 450°C | 0.025 – 0.035″ |
Mica / Glass | |
5108 | 22 – 4/0 | 600 | 250°C | 0.025 – 0.035″ |
Mica / Glass | |
5128 | 24 – 4 | 300 | 450°C | 0.015 – 0.020″ |
Mica / Glass | |
5134 | 22 – 4 | 300 | 250°C | 0.015 – 0.020″ |
Mica / Glass | |
5127 | 24 – 8 | 600 | 250°C | 0.015″ | PTFE Severed Glass / Glass Braid |
|
5180 | 16 – 2 | 300 | 250°C | 0.004 – 0.012″ |
PTFE Severed Glass / Glass Braid |
|
5181 | 24 – 4/0 | 600 | 250°C | 0.020 – 0.045″ |
PTFE / Glass Braid |
|
5259 | 22 – 4/0 | 600 | 250°C | 0.012 – 0.030″ |
Mica / PTFE /Glass Braid |
|
10086 | 32 – 4/0 | 600 | 150°C / 200°C | 0.010 – 0.045″ |
ETFE | |
10109 | 32 – 4/0 | 300 | 150°C / 200°C | 0.006 – 0.045″ |
ETFE | |
10125 | 32 – 4/0 | 300 | 150°C | 0.006 – 0.045″ |
ETFE | |
10126 | 32 – 4/0 | 600 | 150°C | 0.010 – 0.045″ |
ETFE |